See diagram
UWWTP_PIRAN | UWWTD SIIF Slovenia National Node
Beta Version : remaining inconsistencies are possible. They will be corrected during the next reporting exercise

UWWTP_PIRAN

Agglomeration view on a map with some info

UWWTP : UWWTP_PIRAN - Identifier : SI_KCN_00068 - Status : Active - Connected - Reporting year : 2016
Region (NUTS) Code : SI044 - Region (NUTS) Name : SI044

compliance Time Line
List of all the year available for the agglomeration

2012

2014

2016

 
Compliant
 
Not compliant
 
Not relevant
 
No information
 
?


Description
Load entering UWWTP (p.e.): 
load expressed in population equivalent shall be calculated on the basis of the maximum average weekly load entering the treatment plant during the year, excluding unusual situations such as those due to heavy rain (Article 4 of the Urban Waste Water Treatment Directive 91/271/CE)
11 008
Method used to determine the load : 
Not available
Rate of entering load transported to this UWWTP by trucks (%): 
Not available
Physical Capacity (p.e.): 
33 000
Waste water treated (m3/y): 
Volume of waste water treated and partially treated in the UWWTP
1 888 781
Method used to determine the volume of waste water treated: 
M
Treatment performance: BOD5: 
Biological Oxygen Demand
Pass
Treatment performance: COD: 
Chemical Oxygen Demand
Pass
Treatment performance: TSS: 
Total Suspended Solids
Pass
Treatment performance: Total nitrogen: 
Sum of total kjeldahl nitrogen (organic, ammonia and ammonium), nitrate and nitrite
Pass
Treatment performance: Total phosphorus: 
Sum of dissolved phosphorus and insoluble phosphorus
Pass
Treatment performance: Other: 
e.g. e-coli
NR
Compliance: 
Compliant
Treatment type in place: 
More stringent treatment
Treatment required: 
More stringent treatment : Nitrogen and Phosphorus
Treatment met: 
Yes
Performance met: 
Yes
In cause of failure: Bad operating/Bad design or dimensioning: 
0
In cause of failure: Bad design or dimensioning: 
0
In cause of failure: Further information on cause of failure: 
Not available
See diagram

Load and concentration per parameter :

Incoming Discharged Rate
BOD 241.1 t/year 17.5 t/year 92.7%
127.65 mg/l 9.27 mg/l
COD 437.7 t/year 80.6 t/year 81.6%
231.74 mg/l 42.67 mg/l
Nitrogen 52.2 t/year 9.2 t/year 82.4%
27.64 mg/l 4.87 mg/l
Phosphorus 8.7 t/year 2.6 t/year 70.1%
4.61 mg/l 1.38 mg/l
* Concentration calculated using the annual load and the annual volume of wastewater treated.
Incoming and discharged loads (t/year)
See the data table
Graphical network summary
Network
Agglomerations : 2 Agglomeration : SI_LUCIJA_538
(GeneratedAgglomeration : SI_SEČA_540
(Generated
Network
Network
Entering :
11,008 p.e
Network
N
Network
P
Network
    Main treatment :
  • Network : Compliant
  • Network : Not compliant
  • Network : No information / Not relevant
    More stringent treatment :
    Performance :
  • Network : Pass performance
  • Network : Fail performance
  • Network : Not relevant

    Type :
  • N : Nitrogen removal
  • P : Phosphorus removal
  • UV : UV treatment
  • MICRO : Micro Filtration

    Type :
  • CHLOR : Chlorination
  • OZONE : Ozonation
  • SAND : Sand filtration
  • O : Other more stringent
    Discharge point :
  • Network : Discharge point
  • DCP(S) : Discharge point(s)
Waste Water Network Connexions
Linked agglomeration(s): 
Linked receiving area(s): 
Linked discharge point(s): 
Site information
Characteristics
 45.51948800
 13.56951000
Date of closing: 

Not provided

Explanation for closing: 

Not provided

ID of the successor: 

Not provided

Primary treatment: 
Yes
Secondary treatment: 
Yes
N removal: 
Yes
P removal: 
Yes
UV: 
No
Ozonation: 
No
Sand filtration: 
No
Chlorination: 
No
Micro filtration: 
No
Other treatment: 
No
Other type of more stringent treatment: 

Not provided

Other type of more stringent : 

Not provided

ID of E-PRTR facility: 

Not provided

Accidents: 
No
Remarks: 

Not provided

Forward looking aspect
Identified reason(s) for non compliance: 
Investicijsko vzdrževanje čistilne naprave
Measure(s) to reach the compliance needed for UWWTP: 
Investicijsko vzdrževanje čistilne naprave
Load entering the UWWTP at the expected date of compliance (as planned): 
33000
Organic design capacity UWWTP (as planned): 
33000
Type of treatment UWWTP (as planned): 
3NPm
Date or expected date of completion of preparatory measures (planning, design, etc): 
01 January 2013
Date or expected start date for works: 
01 June 2013
Date or expected date of completion of works: 
01 December 2015
Expected date of compliance (12 months of compliant samples) : 
01 December 2016
Forecast cost investment needed for the UWWTP (as in the national plan): 
0.67
Amount of (planned) EU funding needed: 
0.00