See diagram
Ta' Barkat Urban Wastewater Treatment Plant | European Commission urban waste water website: Malta
Beta Version : remaining inconsistencies are possible. They will be corrected during the next reporting exercise

Ta' Barkat Urban Wastewater Treatment Plant

Agglomeration view on a map with some info

UWWTP : Ta' Barkat Urban Wastewater Treatment Plant - Identifier : MTSSTP - Status : Active - Connected - Reporting year : 2014
Region (NUTS) Code : MT001 - Region (NUTS) Name : Malta

compliance Time Line
List of all the year available for the agglomeration

2014

2016

2018

 
Compliant
 
Not compliant
 
Not relevant
 
No information
 
?


Description
Load entering UWWTP (p.e.): 
load expressed in population equivalent shall be calculated on the basis of the maximum average weekly load entering the treatment plant during the year, excluding unusual situations such as those due to heavy rain (Article 4 of the Urban Waste Water Treatment Directive 91/271/CE)
408 967
Method used to determine the load : 
Not available
Rate of entering load transported to this UWWTP by trucks (%): 
Not available
Physical Capacity (p.e.): 
500 000
Waste water treated (m3/y): 
Volume of waste water treated and partially treated in the UWWTP
18 707 130
Method used to determine the volume of waste water treated: 
M
Treatment performance: BOD5: 
Biological Oxygen Demand
Fail
Treatment performance: COD: 
Chemical Oxygen Demand
Fail
Treatment performance: TSS: 
Total Suspended Solids
Fail
Treatment performance: Total nitrogen: 
Sum of total kjeldahl nitrogen (organic, ammonia and ammonium), nitrate and nitrite
NR
Treatment performance: Total phosphorus: 
Sum of dissolved phosphorus and insoluble phosphorus
NR
Treatment performance: Other: 
e.g. e-coli
NR
Compliance: 
Not compliant
Treatment type in place: 
More stringent treatment
Treatment required: 
Secondary treatment
Treatment met: 
Yes
Performance met: 
No
In cause of failure: Bad operating/Bad design or dimensioning: 
0
In cause of failure: Bad design or dimensioning: 
0
In cause of failure: Further information on cause of failure: 
Overload from farmyard waste that was meant to be disconnected from the sewerage network.
See diagram

Load and concentration per parameter :

Incoming Discharged Rate
BOD 8932 t/year 524 t/year 94.1%
477.47 mg/l 28.01 mg/l
COD 16354 t/year 3907 t/year 76.1%
874.21 mg/l 208.85 mg/l
Nitrogen 0 t/year
Phosphorus 0 t/year
* Concentration calculated using the annual load and the annual volume of wastewater treated.
Incoming and discharged loads (t/year)
See the data table
Graphical network summary
Network
Agglomerations : 1 Agglomeration : Malta South
(Generated
Network
Network
N
Network
reseau
1 DCP(S)
Discharge point: Ta' Barkat
(NA)

    Main treatment :
  • Network : Compliant
  • Network : Not compliant
  • Network : No information / Not relevant
    More stringent treatment :
    Performance :
  • Network : Pass performance
  • Network : Fail performance
  • Network : Not relevant

    Type :
  • N : Nitrogen removal
  • P : Phosphorus removal
  • UV : UV treatment
  • MICRO : Micro Filtration

    Type :
  • CHLOR : Chlorination
  • OZONE : Ozonation
  • SAND : Sand filtration
  • O : Other more stringent
    Discharge point :
  • Network : Discharge point
  • DCP(S) : Discharge point(s)
Waste Water Network Connexions
Linked agglomeration(s): 
Linked receiving area(s): 
Not available
Linked discharge point(s): 
Site information
Characteristics
 35.88000000
 14.56000000
Date of closing: 
NR
Explanation for closing: 
NR
ID of the successor: 

Not provided

Primary treatment: 
Yes
Secondary treatment: 
Yes
N removal: 
Yes
P removal: 
No
UV: 
No
Ozonation: 
No
Sand filtration: 
No
Chlorination: 
No
Micro filtration: 
No
Other treatment: 
No
Other type of more stringent treatment: 
Not applicable
Other type of more stringent : 
0
ID of E-PRTR facility: 

Not provided

Accidents: 
No
Remarks: 
Wastewater bypasses took place due to extensive cleaning operations carried out on the plant during the year in view of the receipt of non-domestic wastewater.
Forward looking aspect
Identified reason(s) for non compliance: 
RECEIPT OF UNCONTROLLED FARMYARD WASTE AT THE UWWTP
Measure(s) to reach the compliance needed for UWWTP: 
DISCONNECTION OF FARMYARD WASTE AND/OR PRE-TREATMENT OF SAME BEFORE DISCHARGING TO THE SEWERS
Load entering the UWWTP at the expected date of compliance (as planned): 
500000
Organic design capacity UWWTP (as planned): 
500000
Type of treatment UWWTP (as planned): 
2
Date or expected date of completion of preparatory measures (planning, design, etc): 
31 December 2016
Date or expected start date for works: 
01 January 2016
Date or expected date of completion of works: 
31 December 2017
Expected date of compliance (12 months of compliant samples) : 
31 December 2018
Forecast cost investment needed for the UWWTP (as in the national plan): 
0.00
Name of EU fund planned to be used UWWTP (if any): 
Unknown at this stage
Any relevant comment on UWWTP: 
NO SIGNIFICANT UPGRADE EXPECTED BEFORE 2020