Beta Version : remaining inconsistencies are possible. They will be corrected during the next reporting exercise

Juodkrantes nuoteku valykla - history

UWWTP : Juodkrantes nuoteku valykla - Identifier : LT-AG-072-WWTP-01 - Status : Active
Region (NUTS) Code : LT023 - Region (NUTS) Name : LT023

2011

2014

2018

 
Compliant
 
Not compliant
 
Not relevant
 
No information
 
?


Description

YearComplianceTreatment typeLoadTreatment performance
2011Compliance : Compliant
Treatment met : Yes
Performance met : Yes
required : Secondary treatment
in place : Secondary treatment
Capacity:
3,000 p.e.From field <uwwCapacity> : Organic design capacity (p.e.)
Entering:
720 p.e.From field <uwwLoadEnteringUWWTP> : Load entering UWWTP (p.e.)
Load rate:
24 % underload<uwwLoadEnteringUWWTP> / <uwwCapacity> x 100
BOD:
PassFrom field <uwwBOD5Perf>
COD:
PassFrom field <uwwCODPerf>
TSS:
Not relevantFrom field <uwwTSSPerf>
Total Nitrogen:
Not relevantFrom field <uwwNTotPerf>
Total phosphorus:
PassFrom field <uwwPTotPerf>
Other:
Not relevantFrom field <uwwOtherPerf>
2014Compliance : Not relevant
Treatment met :
Performance met :
required :
in place : Secondary treatment
Capacity:
3,000 p.e.From field <uwwCapacity> : Organic design capacity (p.e.)
Entering:
1,300 p.e.From field <uwwLoadEnteringUWWTP> : Load entering UWWTP (p.e.)
Load rate:
43.3 % underload<uwwLoadEnteringUWWTP> / <uwwCapacity> x 100
BOD:
PassFrom field <uwwBOD5Perf>
COD:
PassFrom field <uwwCODPerf>
TSS:
Not relevantFrom field <uwwTSSPerf>
Total Nitrogen:
Not relevantFrom field <uwwNTotPerf>
Total phosphorus:
Not relevantFrom field <uwwPTotPerf>
2018Compliance : Compliant
Treatment met : Yes
Performance met : Yes
required : Secondary treatment
in place : Secondary treatment
Capacity:
3,000 p.e.From field <uwwCapacity> : Organic design capacity (p.e.)
Entering:
2,183 p.e.From field <uwwLoadEnteringUWWTP> : Load entering UWWTP (p.e.)
Load rate:
72.8 % <uwwLoadEnteringUWWTP> / <uwwCapacity> x 100
BOD:
PassFrom field <uwwBOD5Perf>
COD:
PassFrom field <uwwCODPerf>
TSS:
Not relevantFrom field <uwwTSSPerf>
Total Nitrogen:
Not relevantFrom field <uwwNTotPerf>
Total phosphorus:
Not relevantFrom field <uwwPTotPerf>
Other:
Not relevantFrom field <uwwOtherPerf>

Entering load and design capacity

Entering load vs Physical Capacity (p.e.)
See the data table
Entering load vs Physical Capacity (p.e.)
See diagram
YearEnteringCapacityLoad rate
2011720 p.e.3,000 p.e.24 % underload
20141,300 p.e.3,000 p.e.43.3 % underload
20182,183 p.e.3,000 p.e.72.8 %
Waste water treated (m3/y)
See the data table
Waste water treated (m3/y)
See diagram
YearWaste water treatedDelta
2011135,000 m3/y-
201494,200 m3/y-30.2 %
2018123,574 m3/y31.2 %

COD & BOD

COD load entering and discharged (Tons per year)
See the data table
COD load entering and discharged (Tons per year)
See diagram
YearEnteringDischargedPerformance rate
201139 T/y5 T/y88.0 %
201437 T/y4 T/y90.2 %
2018124 T/y5 T/y96.1 %
BOD load entering and discharged (Tons per year)
See the data table
BOD load entering and discharged (Tons per year)
See diagram
YearEnteringDischargedPerformance rate
201116 T/y1 T/y93.8 %
201429 T/y1 T/y98.2 %
201848 T/y0 T/y99.0 %

Nitrogen & Phosphorus

Nitrogen load entering and discharged (Tons per year)
See the data table
Nitrogen load entering and discharged (Tons per year)
See diagram
YearEnteringDischargedPerformance rate
20115 T/y2 T/y56.3 %
20140 T/y0 T/y-
20180 T/y0 T/y-
Phosphorus load entering and discharged (Tons per year)
See the data table
Phosphorus load entering and discharged (Tons per year)
See diagram
YearEnteringDischargedPerformance rate
20111 T/y0 T/y70.6 %
20140 T/y0 T/y-
20180 T/y0 T/y-

Agglomerations

Year
UWWTP capacity
Value define in <uwwCapacity> field for the UWWTP in the report file with definition : "Organic design capacity (p.e.)"
UWWTP Entering load
Value define in <uwwLoadEnteringUWWTP> field for the UWWTP in the report file with definition : "Load entering UWWTP (p.e.)"
Total of load collected by collecting systems and entering the UWWTPs
Sum of load adressed to UWWTP by linked agglomeration. The load addressed by an agglomeration to an UWWTP is calculated with the following formula : Generated load (p.e.) of the agglomeration (<aggGenerated>) x Rate of generated load of agglomeration collected through collecting system (% of p.e.) (<aggC1>) x % of load of agglomeration collected in collecting system and entering that treatmentplant (<aucPercEnteringUWWTP>)
Linked Agglomeration(s) with addressed load to the UWWTP
20113,000p.e.720p.e.238p.e.
20143,000p.e.1,300p.e.1,277p.e.
20183,000p.e.2,183p.e.2,183p.e.
Notice : "UWWTP entering load" is based on measure of yearly average, "Total of load collected" is based on estimation of maximum over a year.

Discharge points

YearLinked Discharge point(s)
2011
2014
2018