See diagram
Joniskio aglomeracija | UWWTD SIIF Lithuania National Node
Beta Version : remaining inconsistencies are possible. They will be corrected during the next reporting exercise

Joniskio aglomeracija

Agglomeration view on a map with some info

UWWTP : Joniskio aglomeracija - Identifier : LT-AG-038-WWTP-01 - Status : Active - Connected - Reporting year : 2014
Region (NUTS) Code : LT006 - Region (NUTS) Name : Šiaulių apskritis

compliance Time Line
List of all the year available for the agglomeration

2011

2014

2016

2018

 
Compliant
 
Not compliant
 
Not relevant
 
No information
 
?


Description
Load entering UWWTP (p.e.): 
load expressed in population equivalent shall be calculated on the basis of the maximum average weekly load entering the treatment plant during the year, excluding unusual situations such as those due to heavy rain (Article 4 of the Urban Waste Water Treatment Directive 91/271/CE)
8 100
Method used to determine the load : 
Not available
Rate of entering load transported to this UWWTP by trucks (%): 
Not available
Physical Capacity (p.e.): 
22 800
Waste water treated (m3/y): 
Volume of waste water treated and partially treated in the UWWTP
808 800
Method used to determine the volume of waste water treated: 
M
Treatment performance: BOD5: 
Biological Oxygen Demand
Pass
Treatment performance: COD: 
Chemical Oxygen Demand
Pass
Treatment performance: TSS: 
Total Suspended Solids
NR
Treatment performance: Total nitrogen: 
Sum of total kjeldahl nitrogen (organic, ammonia and ammonium), nitrate and nitrite
Pass
Treatment performance: Total phosphorus: 
Sum of dissolved phosphorus and insoluble phosphorus
Pass
Treatment performance: Other: 
e.g. e-coli
Not available
Compliance: 
Compliant
Treatment type in place: 
More stringent treatment
Treatment required: 
Secondary treatment
Treatment met: 
Yes
Performance met: 
Yes
In cause of failure: Bad operating/Bad design or dimensioning: 
0
In cause of failure: Bad design or dimensioning: 
0
In cause of failure: Further information on cause of failure: 
8179,22573
See diagram

Load and concentration per parameter :

Incoming Discharged Rate
BOD 179.13 t/year 2.19 t/year 98.8%
221.48 mg/l 2.71 mg/l
COD 289.89 t/year 28.08 t/year 90.3%
358.42 mg/l 34.72 mg/l
Nitrogen 49.72 t/year 7.31 t/year 85.3%
61.47 mg/l 9.04 mg/l
Phosphorus 6.24 t/year 1.38 t/year 77.9%
7.72 mg/l 1.71 mg/l
* Concentration calculated using the annual load and the annual volume of wastewater treated.
Incoming and discharged loads (t/year)
See the data table
Graphical network summary
Network
Agglomerations : 1 Agglomeration : Joniskis
(Generated
Network
Network
Entering :
8,100 p.e
Network
N
Network
P
Network
    Main treatment :
  • Network : Compliant
  • Network : Not compliant
  • Network : No information / Not relevant
    More stringent treatment :
    Performance :
  • Network : Pass performance
  • Network : Fail performance
  • Network : Not relevant

    Type :
  • N : Nitrogen removal
  • P : Phosphorus removal
  • UV : UV treatment
  • MICRO : Micro Filtration

    Type :
  • CHLOR : Chlorination
  • OZONE : Ozonation
  • SAND : Sand filtration
  • O : Other more stringent
    Discharge point :
  • Network : Discharge point
  • DCP(S) : Discharge point(s)
Waste Water Network Connexions
Linked agglomeration(s): 
Linked receiving area(s): 
Linked discharge point(s): 
Site information
Characteristics
 56.25440000
 23.63120000
Date of closing: 

Not provided

Explanation for closing: 

Not provided

ID of the successor: 

Not provided

Primary treatment: 
Yes
Secondary treatment: 
Yes
N removal: 
Yes
P removal: 
Yes
UV: 
No
Ozonation: 
No
Sand filtration: 
No
Chlorination: 
No
Micro filtration: 
No
Other treatment: 
No
Other type of more stringent treatment: 

Not provided

Other type of more stringent : 
0
ID of E-PRTR facility: 

Not provided

Accidents: 
No
Remarks: 

Not provided