Agglomeration view on a map with some info UWWTP : Kaisiadoriu nuoteku valykla - Identifier : LT-AG-027-WWTP-01 - Status : Active - Connected - Reporting year : 2018 Region (NUTS) Code : LT022 - Region (NUTS) Name : LT022 compliance Time Line List of all the year available for the agglomeration 2011201420162018View history Compliant Not compliant Not relevant No information ? Description Load entering UWWTP (p.e.): load expressed in population equivalent shall be calculated on the basis of the maximum average weekly load entering the treatment plant during the year, excluding unusual situations such as those due to heavy rain (Article 4 of the Urban Waste Water Treatment Directive 91/271/CE)22 146Method used to determine the load : Not availableRate of entering load transported to this UWWTP by trucks (%): Not availablePhysical Capacity (p.e.): 20 000Waste water treated (m3/y): Volume of waste water treated and partially treated in the UWWTP1 168 290Method used to determine the volume of waste water treated: MTreatment performance: BOD5: Biological Oxygen DemandPassTreatment performance: COD: Chemical Oxygen DemandPassTreatment performance: TSS: Total Suspended SolidsNRTreatment performance: Total nitrogen: Sum of total kjeldahl nitrogen (organic, ammonia and ammonium), nitrate and nitritePassTreatment performance: Total phosphorus: Sum of dissolved phosphorus and insoluble phosphorusPassTreatment performance: Other: e.g. e-coliNRCompliance: CompliantTreatment type in place: More stringent treatmentTreatment required: More stringent treatment : Nitrogen and PhosphorusTreatment met: YesPerformance met: YesIn cause of failure: Bad operating/Bad design or dimensioning: Not availableIn cause of failure: Bad design or dimensioning: Not availableIn cause of failure: Further information on cause of failure: Not available Load and concentration per parameter : Incoming Discharged Rate BOD 485 t/year 3.88 t/year 99.2% 415.14 mg/l 3.32 mg/l COD 1229.21 t/year 38.46 t/year 96.9% 1052.14 mg/l 32.92 mg/l Nitrogen 70.82 t/year 10.92 t/year 84.6% 60.62 mg/l 9.35 mg/l Phosphorus 6.26 t/year 0.29 t/year 95.4% 5.36 mg/l 0.25 mg/l * Concentration calculated using the annual load and the annual volume of wastewater treated. Incoming and discharged loads (t/year) Graphical network summary Agglomerations : 1 Agglomeration : Kaisiadorys (Generated Kaisiadoriu nuoteku valykla Entering :22,146 p.e NP 1 DCP(S)Discharge point: Kaisiadoriu m. isleistuvasLithuania(A58) Main treatment : : Compliant : Not compliant : No information / Not relevant More stringent treatment : Performance : : Pass performance : Fail performance : Not relevant Type : N : Nitrogen removal P : Phosphorus removal UV : UV treatment MICRO : Micro Filtration Type : CHLOR : Chlorination OZONE : Ozonation SAND : Sand filtration O : Other more stringent Discharge point : : Discharge point DCP(S) : Discharge point(s) Waste Water Network Connexions Linked agglomeration(s): KaisiadorysLinked receiving area(s): LithuaniaLinked discharge point(s): Kaisiadoriu m. isleistuvas Site information Year of data: 2018 Source of data: See sourcefile Other years : Year of data: 2016 Source of data: See sourcefile Year of data: 2014 Source of data: See sourcefile Year of data: 2011 Source of data: See sourcefile UWWTP national Internet hyperlink: Not available Characteristics Latitude : 54.87110000 Longitude : 24.44280000 Date of closing: Not providedExplanation for closing: Not providedID of the successor: Not providedPrimary treatment: Secondary treatment: N removal: P removal: UV: Ozonation: Sand filtration: Chlorination: Micro filtration: Other treatment: Other type of more stringent treatment: Not providedOther type of more stringent : Not providedID of E-PRTR facility: Not providedAccidents: Not availableRemarks: Not provided Errors: Not provided